(1) To facilitate the ingress and egress of emergency vehicles, all roads shall be a minimum width of 30 feet and looped, not dead ending in a cul-de-sac, unless the cul-de-sac shall be of sufficient size as to permit the turnaround of a fire department pumper without backing up.

(2) Fire hydrants with steamer ports shall be installed at every intersection not less than 500 feet apart with the first hydrant located within 500 feet of an existing town of Cathlamet fire hydrant. Mains shall be looped and a minimum of eight inches in diameter, and comply with water system standards of the current regional water system plan.

(3) There shall be at least two entrances and exits to the park fronting upon public roadways and located on opposite sides of the park in order to facilitate access by emergency vehicles from two directions.

(4) All spaces shall be marked at the street with visible address numbers constructed of a highly reflective material with numerals at least six inches high.

(5) All streets shall be named and signed at each intersection with names approved by the town of Cathlamet.

(6) A complete set of plans and specifications of the manufactured home park shall be provided to the fire department showing each lot and building placed thereon with exterior dimensions and interior floor plans. Interior plans shall be on separate drawings 8-1/2 inches by 11 inches in size with the address in one inch block letters at the top. Updated plans and specifications shall be provided to the fire department each time a manufactured home or other structure is added to the manufactured home park or removed from the manufactured home park. (Ord. 373 § 9, 1996)